JBKH-30ZSN1-ultra-low temperature heat pump heating machine (frequency conversion)
Heat pump air conditioning
Heat pump series
Commercial heating
- Details Introduction
-
- Commodity name: JBKH-30ZSN1-ultra-low temperature heat pump heating machine (frequency conversion)
Thermal King series is designed for commercial sites, using low-temperature enthalpy technology, equipped with the latest inverter compressor, modular design, can achieve multi-machine combination, while the unit is energy-saving and reliable, can work continuously for a long time.
Heat King series is a model designed for commercial places,
The use of low-temperature enthalpy technology, the configuration of the latest inverter compressor,
Modular design, can achieve multi-machine combination, while the unit energy-saving and reliable,
Can work continuously for a long time.
• Ultra-low temperature operation
Low temperature enthalpy increase frequency conversion technology, ultra-low temperature -35 ℃ stable operation
• Stable and reliable
Efficient shell and tube heat exchanger, complete heat exchange, long life
• Freeze protection
Real-time monitoring of water temperature, automatic start of antifreeze function
• Intelligent defrosting
Leading frost control technology, defrosting clean


Specifications:
Model
KBKH-35ZIS
KBKH-72ZIS
Rated heating capacity (kw)
105
175
Rated heating input power (kw)
32.8
53.5
Rated heating input current (A)
54
88
Nominal heating capacity (kw)
70
135
Nominal heating input power (kw)
29.1
57.7
Nominal heating input current (A)
44.2
95
Low temperature heating capacity (kw)
56.2
112
Low temperature heating input power (kw)
28.9
55.6
Low temperature heating input current (A)
47.6
91.6
Rated cooling capacity (kw)
68
135
Rated refrigeration input power (kw)
27.2
53.6
Rated cooling input current (A)
41.3
88.2
IPLV(H)
2.92
2.89
Power supply specifications (V/Hz)
380V3N〜/50/Hz
The most lost power (kw)
40
86
The most lost current (A)
60
138.2
Maximum water temperature (℃)
55
55
Adaptation to ambient temperature (℃)
-35℃~48℃
Side pressure loss of water supply (KPa)
70
70
Pipe diameter of circulating water supply pipe
DN80
DN80
Host weight (kg)
877
1140
Noise (dB(A))
≤67
≤69
Shape ruler (mm)
1965×1030×2160
2400×1160×2530
Circulating water flow (m3/h)
12
23
Main power cord specifications (mm2)
16
25
Note:1.Nominal Cooling Condition: Outdoor Temperature35/-℃, out-of-water temperature7℃;
2.Nominal Heating Condition: Outdoor Temperature-12/-14℃, out-of-water temperature41℃;
3.Rated heating condition: outdoor temperature7/6℃, out-of-water temperature45℃;
The product parameters, appearance and ruler may be updated and upgraded for reference only. Please refer to the nameplate of the fuselage and the actual product.
Key words:
Lean equipment
Product Message
Get in touch with our team in a timely manner and be happy You offer help
* Note: Please be sure to fill in the information accurately and keep the communication unblocked. We will get in touch with you as soon as possible.